Maintenance and Troubleshooting

Chapter 5

5Ć10

Table 5.B

Troubleshooting Chart

Controller

Troubleshooting Indicators

Mode[1]

Processor

Memory

Run

DC ON

Procedures to Correct Fault

ON

OFF

OFF

ON

1. Cycle line power.

2. Replace Processor

T, R,

or R/P

OFF

OFF

OFF

OFF

1. Check Power Supply fuse.

2. Check AC line voltage.

3. Cycle line power.

4. Verify Power supply load

does not exceed 6.5A

5. Replace System Power Supply

T or R

ON

ON

OFF

ON

1. Connect Industrial Terminal to

Processor and turn Mode Select

Switch to PROG.

2. If a run-time error occurred,

correct it.

3. If a Processor fault occurred, turn

keyswitch back to TEST or RUN.

4. Replace Processor

R or R/P

OFF

OFF

OFF

ON

1. Check AC line voltage.

2. Measure Power Supply output

voltages. Replace Power Supply.

3. Measure voltages through I/O

Power Cable. Replace I/O Power

Cable.

4. Replace Processor.

R/P

OFF

ON

OFF

ON

1. Connect Industrial Terminal to

Processor.

2. Correct run-time error.

R/P

ON

ON

OFF

ON

1. Turn Mode Select Switch to PROG

and back to RUN/PROG.

2. Replace Processor.

[1] T = TEST POSITION

R = RUN POSITION

R/P = RUN/PROGRAM POSITION