Rockwell Automation 1772-LV,D17726.6.1 A and I MNL MINI-PLC-2/15 PROCESSO User Manual

Page 73

Advertising
background image

Maintenance and Troubleshooting

Chapter 5

5Ć3

Table 5.A

Recommended Spare Parts

Quantity

Cat. No.

Description

POWER SUPPLY

1

1770-XO

Lithium Battery

or

2

1771-BA

D-size Alkaline Battery

1

1771-BB

Battery Pack (includes 2 alkaline batteries)

1

1771-CL

I/O Power Cable (1 ft./30.5 cm)

1

1771-CM

I/O Power Cable (5 ft./1.5 m)

1

1771-FP

Fuse Package for Power Supply; includes
5 1A slow-blow fuses for 120V use
5 0.5A slow-blow fuses for 220/240V use

1

1771-P1

System Power Supply

PROCESSOR

2

1770-XP

EPROM memory, 2048 word capacity

1

1772-CD

Mini-PLC-2/15 Processor Transport Cable
(1 ft./30.5 cm)

1

1772-LV

Mini-PLC-2/15 Processor

1

1772-TC

Program Panel Interconnect Cable
(10ft./3.05 m)

I/O

1 or 10%

1771-

1771 I/O Modules

1

1771-FC

Fuse Package for 1771 I/O Modules (five
2A, 120V Fuses)

Power Supply Fuse Replacement

If the AC line fuse has blown, the cause of the blown fuse must be corrected
and the fuse must be replaced. Follow these steps to replace a blown Power
Supply fuse:

WARNING: Contact with AC line voltages may cause injury to
personnel. Always remove system power at the main disconnect
before replacing the Power Supply fuse.

Advertising