Maintenance and Troubleshooting

Chapter 5

5Ć9

System Power Supply Replacement

The System Power Supply should be replaced if it is unable to provide the
correct output voltages to power the Processor and I/O Modules. perform the
following steps to replace the Power Supply:

1.

Turn the Processor’s Mode Select Switch to the PROG mode and support
Processor memory.

D

ARE
OUTPUT DEVICES
ON WHEN THEY
SHOULD BE OFF
?

OUTPUT DEVICES ARE
OFF WHEN THEY SHOULD
BE ON

IS
THE OUTPUT
MODULE
INDICATOR
ON ?

IS
ANY FUSE
BLOWN
INDICATOR
ON ?

YES

TURN MODE SELECT SWITCH
TO TEST OR OPERATE REMOTELY
BY PRESSING [SEARCH]
[5] [9] [1]

CHECK FOR SHORTED WIRING
TO OUTPUT DEVICE

CHECK FOR SHORTED
WIRING TO OUTPUT DEVICE

REAPPLY I/O POWER
IF NECESSARY

IS
THE OUTPUT
MODULE
INDICATOR
ON ?

YES

REMOVE I/O POWER
DISCONNECT WIRING AT
FIELD WIRING ARM
TERMINAL RESTORE
I/O POWER

IS
THE OUTPUT
MODULE
INDICATOR
ON ?

REMOVE SYSTEM POWER AND
I/O POWER REPLACE OUTPUT
MODULE RESTORE SYSTEM
POWER AND I/O POWER

RESTART CONTROLLER
VERIFY PROPER OPERATION

CHECK WIRING TO
OUTPUT DEVICE FOR
OPEN CIRCUIT

REMOVE SYSTEM POWER
AND I/O POWER. CORRECT
CAUSE OF BLOWN FUSE
–– CHECK OUTPUT DEVICE
AND WIRING

REPLACE BLOWN FUSE. RESTORE
SYSTEM POWER AND I/O POWER

RESTART CONTROLLER
VERIFY PROPER OPERATION

REMOVE SYSTEM AND I/O POWER
REPLACE OUTPUT MODULE.
RESTORE SYSTEM AND I/O POWER

REMOVE SYSTEM POWER AND
I/O POWER CHECK AND RESET
MODULE IN I/O CHASSIS
RESTORE SYSTEM POWER
AND I/O POWER

IS
PROBLEM
SOLVED
?

RESTART CONTROLLER
VERIFY PROPER OPERATION

NO

YES

YES

NO

NO

YES

NO

NO

NO

YES