Configuring the KFC15 Module

2-3

1747-5.34 - June 1998

Documented in the tables below are the DIP switches, the bank in which
they are located, and the parameters controlled by each switch.

Table 2-1: Bank S1 DIP Switches

Table 2-2: Bank S2 DIP Switches

DIP Switch

Parameter

Description

Switches 1-3

Upper digit of
the DF1 station
address

SW 1/4

on
off
on
off
on
off
on
off

SW 2/5

on
on
off
off
on
on
off
off

SW 3/6

on
on
on
on
off
off
off
off

Digit

0
1
2
3
4
5
6

7 (default)

Switches 4-6

Lower digit of
DF1 station
address

Switches 7-8

Leave off

DIP Switch

Parameters

Description

Switches 1-3

Serial Port
Baud Rate

Switch 1

off
off
off
off
on
on
on
on

Switch 2

off
off
on
on
off
off
on
on

Switch 3

off
on
off
on
off
on
off
on

Baud Rate

1200 (default)

2400
4800
9600

19200
38400
57600

Reserved

Switch 4

Full/Half
duplex

off = Full duplex (default)
on = Half duplex

Switch 5

Parity

off = No parity (default)
on = See switch 6

Switch 6

Odd/Even
parity (when
used with
Switch 5)

off = Odd parity
on = Even parity

Switch 7

Handshake

off = No handshake (default)
on = Hardware handshake enable

Switch 8

Diagnostic
Command
Execution

off = Disabled (default)
on = Enabled