5-2

Troubleshooting the KFC15 Module

1747-5.34 - June 1998

The following terms are used to describe the state of the LEDs:

solid - on continuously in the defined state

flashing - each LED alternates between the two defined states (or with
OFF if only one state is defined). This only applies to a single LED
viewed independently of the other. If both ControlNet LEDs are flashing,
they flash together (in phase).

railroad - both LEDs alternate between the two defined states at the same
time. This only applies to both ControlNet LEDs when viewed together.
The two LEDs are always in opposite states (out-of-phase).

flickering - intermittent on/off between the two states, often in an erratic
pattern

LED

State

Probable Cause

Recommended Action

Channels A
and B
(viewed
together)

OFF

No power or reset

SOLID RED

Failed unit

Check network setup then cycle
power to the KFC15 module. If
the fault persists, contact your
authorized Allen-Bradley
representative or distributor.

RAILROAD RED -
GREEN

Self test

None

RAILROAD RED -
OFF

Incorrect node
configuration

(duplicate node, ID,
etc.)

Check network address and
other ControlNet configuration
parameters.