background image

DF1 Diagnostic Command Support

C-3

1784-5.34 - June 1998

Table C.5: Reply Values

Diagnostic Status

This command requests a block of status information from an RS-232C
device. The reply contains the information in its DATA field. The status
information varies from device to device. The status block is shown
below.

Table C.6: Command Format

Table C.7: Reply Format

1

Total DF1 packets received, low byte

2

Total DF1 packets received, high byte

3

Total DF1 packets transmitted, low byte

4

Total DF1 packets transmitted, high byte

5

Number of DF1 retries

6

Number of DF1 packets where the retry limit was exceeded

7

Number of DF1 NAKs sent

8

Number of DF1 NAKs received

9

Number of DF1 bad messages received

10

Number of RS–232C line errors

11

Total good ControlNet packets received, low byte

12

Total good ControlNet packets received, high byte

13

Total bad ControlNet packets received, low byte

14

Total bad ControlNet packets received, high byte

15

Total ControlNet packets transmitted, low byte

16

Total ControlNet packets transmitted, high byte

1 byte

1 byte

2 bytes

1 byte

CMD
06

STS

TNS

FNC
03

1 byte

1 byte

2 bytes

24 bytes

CMD
46

STS

TNS

DATA

Advertising