Troubleshooting the KFC15 Module

1747-5.34 - June 1998

If the displays show symbols other than those shown in this chapter, this
also indicates that the module is malfunctioning. In this case, contact your
Allen-Bradley representative.

During the power-up of the KFC15, the display shows the serial port
parameters based on the DIP switch settings. Refer to Chapter 2 for
details on these parameters.

This

number

Indicates this fault

Meaning

1

Processor Fault

A hardware fault was detected in the processor.

This is a major fault. Return the KFC15 for servicing.

2

Invalid Firmware

The Flash EPROM does not contain valid firmware. New
firmware must be downloaded to the unit.

3

Firmware Checksum
Fault

A checksum error was detected in the main application
code of the Flash EPROM.

4

RAM Fault

The static RAM cannot be written to reliably or a parity
error has occurred. Cycle power to the KFC15.

If the problem persists, return the KFC15 for servicing.

5

Flash EPROM Write
Fault

The Flash EPROM could not be programmed correctly
during download of new firmware.

This is a major fault. Return the KFC15 for servicing.

9

Invalid Network
Address

The chosen network address is greater than the highest
network address ControlNet is configured for.

10

Duplicate Network
Address

There is a device on the ControlNet network with the
same address.

11

Unrecoverable
Firmware Error

Failed to re-program the boot block of the Flash EPROM.
Return the KFC15 module for servicing.