Rockwell Automation 1794-IE4XOE2,1794-IE8,1794-OE4,D17946.5.2 FLEX I/O ANALOG MODULE User Manual

Page 16

Advertising
background image

2–3

How to Install Your Analog Module

Publication 1794Ć6.5.2 - May 1996

Methods of wiring the terminal base units are shown in the
illustration below.

Wiring when total current draw is less than 10A

Wiring when total current draw is greater than 10A

DaisyĆchaining

Individual

Total current draw through any base unit must not be greater than 10A

Combination

24V dc

24V dc

24V dc

24V dc

24V dc or

120V ac

24V dc

ATTENTION: Do not daisy chain power or
ground from an analog terminal base unit to any ac
or dc discrete module terminal base unit.

!

Note: Use this configuration if using any

noisy" dc discrete I/O modules in your system.

Analog module wiring separate from discrete wiring.

Analog Module

Note: All modules powered by the same power supply

must be analog modules for this configuration.

Note: All modules must be analog modules for this configuration.

Analog Module

Discrete

Module

Discrete

Module

Discrete

Module

Discrete

Module

Analog Module

Analog Module

Analog Module

Analog Module

Analog Module

Analog Module

Advertising