Rockwell Automation 1794-IE4XOE2,1794-IE8,1794-OE4,D17946.5.2 FLEX I/O ANALOG MODULE User Manual

Page 38

Advertising
background image

4–6

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794Ć6.5.2 - May 1996

4 Output Analog Module (Cat. No. 1794ĆOE4 Series B)

Module Image

I/O Image

Analog Data Channel 0
Analog Data Channel 1
Analog Data Channel 2
Analog Data Channel 3

Channel 0 Safe State

Not used

Not used

Not used

Not used

Not used
Not used
Not used
Not used

Diagnostics

Config. Select

Full Range

Input Size

Output Size

0 or 1 Word

1 to 14 Words

Read

Write

M

PU

Channel 1 Safe State
Channel 2 Safe State
Channel 3 Safe State

Analog Output Module (1794-OE4/B) Read

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Read Word 0

PU

Not used - set to 0

W3 W2 W1 W0

Where:

W = Diagnostic bits for current output wire broken or load resistance high. (Not used on voltage outputs.)

PU = Power up bit

Bit/Word Descriptions for the 1794-OE4/B Analog Output
Module Read

Word

Decimal Bit

(Octal Bit)

Definition

Bits 00Ć03

Current outputs only - When set (1), the wire on the output is broken or the

load resistance is too high. Bit 00 corresponds to channel 0, bit 01

corresponds to channel 2, and so on.

Read

Word 0

Bits 04Ć14

(04-16)

Not used - set to 0

Word 0

Bit 15 (17)

Power Up bit - included in series B modules only. This bit is always 0 in

series A modules. This bit is set to 1 when all bits in the configuration

register (write word 5) are 0 (unconfigured state). The configuration

register can be cleared by either a reset, or by the user writing all zeroes to it.