Definition
Decimal Bit
(Octal Bit)
Word
Words 4
and 5
Not used - set to 0.
Word 6
Bits 00-14
(00-16)
Channel 0 Safe State analog value - 12Ćbit left justified two's complement number;
unused lower bits are zero; 4Ć20mA uses all 16 bits.
Word 6
Bits 15 (17)
Channel 0 Safe State analog data sign bit.
Word 7
Bits 00-14
(00-16)
Channel 1 Safe State analog value - 12Ćbit left justified two's complement number;
unused lower bits are zero; 4Ć20mA uses all 16 bits.
Word 7
Bits 15 (17)
Channel 1 Safe State analog data sign bit.