background image

4–12

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794Ć6.5.2 - May 1996

Definition

Decimal Bit

(Octal Bit)

Word

Words 4

and 5

Not used - set to 0.

Word 6

Bits 00-14

(00-16)

Channel 0 Safe State analog value - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 6

Bits 15 (17)

Channel 0 Safe State analog data sign bit.

Word 7

Bits 00-14

(00-16)

Channel 1 Safe State analog value - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 7

Bits 15 (17)

Channel 1 Safe State analog data sign bit.