Analog data format – Rockwell Automation 1794-IE4XOE2,1794-IE8,1794-OE4,D17946.5.2 FLEX I/O ANALOG MODULE User Manual

Page 65

Advertising
background image

Data Table Formats

C–2

Publication 1794Ć6.5.2 - May 1996

The data returned from the analog-to-digital converter in the module
is 12-bit resolute. This value is left-justified into a 16-bit field,
reserving the most significant bit for a sign bit.

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

11 10 09 08 07 06 05 04 03 02 01 00

S

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

10 09 08 07 06 05 04 03 02 01 00

S

S

14 13 12 11 10 09 08 07 06 05 04 03 02 01 00

11 10 09 08 07 06 05 04 03 02 01 00

0*

A/D Unipolar Data

Analog Value

A/D Bipolar Data

Analog Value

D/A Data

Analog Value

⇓ ⇓

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

⇓ ⇓

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

⇓ ⇓

⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓ ⇓

*

= Always positive

Output

Input

Current (mA)

4-20mA Mode 0-20mA Mode

Voltage (V)

+10 Volt Mode

0-10 Volt

M d

Current (mA)

4-20mA Mode 0-20mA Mode

Voltage (V)

Input

Output

0 10 Volt

Mode

-10.50

8000

8000

0.00

0000

-10.00

8620

8618

1.00

0618

-9.00

9250

9248

2.00

0C30

-8.00

9E80

9E78

3.00

1248

-7.00

AAB0

AAA8

4.00

0000

1860

-6.00

B6E0

B6D8

5.00

0787

1E78

-5.00

C310

C310

6.00

0F0F

2490

-4.00

CF40

CF40

7.00

1696

2AA8

-3.00

DB70

DB70

8.00

1E1E

30C0

-2.00

E7A0

E7A0

9.00

25A5

36D8

-1.00

F3D0

F3D0

10.00

2D2D

3CF0

0.00

0000

0000

0000

11.00

34B4

4310

1.00

0C30

0C30

0C30

12.00

3C3C

4928

2.00

1860

1860

1860

13.00

43C3

4F40

3.00

2490

2490

2490

14.00

4B4B

5558

4.00

30C0

30C0

30C0

15.00

52D2

5B70

5.00

3CF0

3CF0

3CF0

16.00

5A5A

6188

6.00

4920

4928

4928

17.00

61E1

67A0

7.00

5550

5558

5558

18.00

6969

6DB8

8.00

6180

6188

6188

19.00

70F0

73D0

9.00

6DB0

6DB8

6DB8

20.00

7878

79E8

10.00

79E0

79E8

79E8

21.00

7FFF

7FF8

10.50

7FF0

7FF8

7FF8

Analog Data Format

Advertising