Specifications

A–6

Publication 1794Ć6.5.2 - May 1996

Specifications - 1794ĆIE4XOE2/B 4 Input/2 Output Analog Combo Module

Current Load on Voltage Output

3mA maximum

Resistive Load on mA Output

15 Ć 750 ohms

Absolute Accuracy

1

Voltage Terminal

Current Terminal

0.133% Full Scale @ 25

o

C

0.425% Full Scale @ 25

o

C

Accuracy Drift with Temperature

Voltage Terminal

Current Terminal

0.0045% Full Scale/

o

C

0.0069% Full Scale/

o

C

General Specifications

Module Location

Cat. No. 1794ĆTB2, ĆTB3 Terminal Base Unit

Flexbus Current

20mA

Power Dissipation

4.0W maximum @ 31.2V dc

Thermal Dissipation

Maximum 13.6 BTU/hr @ 31.2V dc

Keyswitch Position

5

Calibration

None Required

Indicators

1 green power indicator

Isolation Voltage

Tested at 850V dc for 1s between user and system

No isolation between individual channels

External dc Power

Supply Voltage

Voltage Range

Supply Current

24V dc nominal

19.2 to 31.2V dc (includes 5% ac ripple)

70mA @ 24V dc

Dimensions

Inches

(Millimeters)

1.8H x 3.7W x 2.1D

(45.7 x 94.0 x 53.3)

Environmental Conditions

Operational Temperature

Storage Temperature

Relative Humidity

Shock Operating

NonĆoperating

Vibration

0 to 55

o

C (32 to 131

o

F)

-40 to 85

o

C (-40 to 185

o

F)

5 to 95% noncondensing (operating)

5 to 80% noncondensing (nonoperating)

30 g peak acceleration, 11(+1)ms pulse width

50 g peak acceleration, 11(+1)ms pulse width

Tested 5 g @ 10-500Hz per IEC 68Ć2Ć6

Conductors Wire Size

Category

12 gauge (4mm

2

) stranded maximum

3/64 inch (1.2mm) insulation maximum

2

2

Agency Certification

(when product or packaging is marked)

CSA certified

CSA Class I, Division 2, Groups A, B, C, D certified

UL listed

CE marked for all applicable directives

Installation Instruction

Publication 1794Ć5.15

1

Includes offset, gain, nonĆlinearity and repeatability error terms.

2

Use this conductor category information for planning conductor routing as described in publication 1770Ć4.1, Wiring and

Grounding Guidelines for Noise Immunity."