Configuring Your Module and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794Ć6.5.2 - May 1996

Range Selection Bits for the 1794-IE4XOE2/B Analog Combo
Module

Channel No.

Input

Channel 0

Input

Channel 1

Input

Channel 2

Input

Channel 3

Output

Channel 0

Output

Channel 1

F0

C0

F1

C1

F2

C2

F3

C3

F4

C4

F5

C5

Decimal Bits

(Octal Bits)

00

08

(10)

01

09

(11)

02

10

(12)

03

11

(13)

04

12

(14)

05

13

(15)

4-20mA

0

1

0

1

0

1

0

1

0

1

0

1

0-10V dc/0-20mA

1

0

1

0

1

0

1

0

1

0

1

0

Ć10 to +10V dc

1

1

1

1

1

1

1

1

1

1

1

1

Off

1

0

0

0

0

0

0

0

0

0

0

0

0

C = Configure select bit

F = Full range bit

1

When configured to off, individual channels will return or send either 0V or 0mA on Series B modules. On Series modules, 2V or 4mA is output

until the module is configured.

Word/Bit Descriptions for the 1794-IE4XOE2/B Analog Combo
Module Write

Word

Decimal Bit

(Octal Bit)

Definition

Write

Bits 00-14

(00-16)

Channel 0 analog data - 12Ćbit left justified two's complement number; unused

lower bits are zero; 4Ć20mA uses all 16 bits.

Write

Word 0

Bits 15

(17)

Channel 0 analog data sign bit.

Word 1

Bits 00-14

(00-16)

Channel 1 analog data - 12Ćbit left justified two's complement number; unused

lower bits are zero; 4Ć20mA uses all 16 bits.

Word 1

Bits 15

(17)

Channel 1 analog data sign bit.

Word 2

Bits 00-01

Multiplex control bits (M) for individual channels. These bits control the safe state

analog outputs - Bit 00 corresponds to output channel 0, and bit 01 corresponds to

output channel 1.

1 = use words 0 and 1 (analog value) as directed by channel number n

0 = use words 6 and 7 (safe state analog value) as directed by channel number n

When bits 00Ć01 are all cleared (0) simultaneously by a communication error or user

choice thru the programmable controller program, word 3 full range and configure

select bits are preserved at their last setting.

Bits 02-15

(02-17)

Not used - set to 0.

Bits 00-05

Full range bits (F) for individual channels - Bit 00 corresponds to input channel 0,

bit 01 corresponds to input channel 1, bit 02 corresponds to input channel 3, bit 03

corresponds to input channel 3, bit 04 corresponds to output channel 1, and bit 05

corresponds to output channel 2. Refer to Range Bit Selections.

Bits 06Ć07

Not used - set to 0.

Word 3

Bits 08-13

(10Ć15)

Configure select bits (C) for individual channels - Bit 08 corresponds to input

channel 0, bit 09 (11) corresponds to input channel 1, bit 10 (12) corresponds to

input channel 2, bit 11 (13) corresponds to input channel 3, bit 12 (14) corresponds

to output channel 0, and bit 13 (15) corresponds to output channel 1. Refer to Range

Bit Selections.

Bits 14Ć15

(16Ć17)

Not used - set to 0.