How to Install Your Analog Module

Publication 1794Ć6.5.2 - May 1996

5. Rotate the terminal base onto the DIN rail with the top of the rail

hooked under the lip on the rear of the terminal base.

Use caution

to make sure that the female flexbus connector does not strike
any of the pins in the mating male connector.

6. Press the terminal base down onto the DIN rail until flush. The

locking tab D will snap into position and lock the terminal base to
the DIN rail.

7. If the terminal base does not lock in place, use a screwdriver or

similar device to move the locking tab down, press the terminal
base flush with the DIN rail and release the locking tab to lock
the base in place.

8. Gently push the female flexbus connector C into the adjacent

terminal base or adapter female connector to complete the flexbus
connections.

9. Repeat the above steps to install the next terminal base.

Panel/Wall Mounting

Installation on a wall or panel consists of:

laying out the drilling points on the wall or panel

drilling the pilot holes for the mounting screws

mounting the adapter mounting plate

installing the terminal base units and securing them to the wall or
panel

If you are installing your module into a terminal base unit that is
already installed, proceed to “Mounting the Analog Module on the
Terminal Base” on page 2–7.

Use the mounting kit Cat. No. 1794-NM1 for panel/wall mounting.

1.4

(35.5)

1

1794ĆNM1 Mounting Kit

Contents:

1 - Mounting Plate for Adapter

2 - 18 #6 selfĆtapping screws

(2 for the adapter, and 2

each for up to 8 modules)

2

Adapter Module

(not included)

Terminal Base Unit

(not included)