background image

4–4

Writing Configuration to and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794Ć6.5.2 - May 1996

Word/Bit Descriptions for the 1794-IE8 Analog Input Module
Read

Word

Decimal Bit

(Octal Bit)

Definition

Read Word 0

Bits 00-14

(00-16)

Channel 0 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Read Word 0

Bits 15 (17)

Channel 0 analog data sign bit.

Word 1

Bits 00-14

(00-16)

Channel 1 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 1

Bits 15 (17)

Channel 1 analog data sign bit.

Word 2

Bits 00-14

(00-16)

Channel 2 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 2

Bits 15 (17)

Channel 2 analog data sign bit.

Word 3

Bits 00-14

(00-16)

Channel 3 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 3

Bits 15 (17)

Channel 3 analog data sign bit.

Word 4

Bits 00-14

(00-16)

Channel 4 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 4

Bits 15 (17)

Channel 4 analog data sign bit.

Word 5

Bits 00-14

(00-16)

Channel 5 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 5

Bits 15 (17)

Channel 5 analog data sign bit.

Word 6

Bits 00-14

(00-16)

Channel 6 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 6

Bits 15 (17)

Channel 6 analog data sign bit.

Word 7

Bits 00-14

(00-16)

Channel 7 analog data - 12Ćbit left justified two's complement number;

unused lower bits are zero; 4Ć20mA uses all 16 bits.

Word 7

Bits 15 (17)

Channel 7 analog data sign bit.

Bits 00-07

Underrange bits (U) for individual channels (4Ć20mA current input only)-

Bit 00 corresponds to input channel 0, bit 01 corresponds to input channel 1,

and so on. When set (1), indicates either a broken or open input wire, or input

current at or below 4mA.

Word 8

Bits 08Ć14

(10Ć16)

Not used - set to 0.

Bit 15 (17)

Power Up bit - included in series B modules only. This bit is always 0 in

series A modules. This bit is set to 1 when all bits in the configuration

register (write word 0) are 0 (unconfigured state). The configuration

register can be cleared by either a reset, or by the user writing all zeroes to it.

Analog Input Module (1794-IE8/B) Write Configuration Block

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Write Word 0

C7

C6

C5

C4

C3

C2

C1

C0

F7

F6

F5

F4

F3

F2

F1

F0

Where:

C = Configure select bit

F = Full range bit