5–2

How Communication Takes Place and I/O Image Table Mapping with the DeviceNet Adapter

Publication 1794Ć6.5.2 - May 1996

Adapter Input Status Word

The input status word consists of:

I/O module fault bits – 1 status bit for each slot

node address changed – 1 bit

I/O status – 1 bit

15

Bit:

0

1

2

3

4

5

6

7

8

10 through 15

I/O Module Fault Bits

Node Address Changed Bit

Slot 0

Slot 1

Slot 2

Slot 3

Slot 4

Slot 5

Slot 6

Slot 7

9

I/O State Bit

Not Used

The adapter input status word bit descriptions are shown in the
following table.

Bit Description

Bit

Explanation

0

This bit is set (1) when an error is detected in slot position 0.

1

This bit is set (1) when an error is detected in slot position 1.

2

This bit is set (1) when an error is detected in slot position 2.

I/O Module Fault

3

This bit is set (1) when an error is detected in slot position 3.

I/O Module Fault

4

This bit is set (1) when an error is detected in slot position 4.

5

This bit is set (1) when an error is detected in slot position 5.

6

This bit is set (1) when an error is detected in slot position 6.

7

This bit is set (1) when an error is detected in slot position 7.

Node Address Changed

8

This bit is set (1) when the node address switch setting has been

changed since power up.

I/O State

9

Bit = 0 - idle

Bit = 1 - run

10 thru 15 Not used - sent as zeroes.

Possible causes for an I/O Module Fault are:

transmission errors on the FLEX I/O backplane

a failed module

a module removed from its terminal base

incorrect module inserted in a slot position

the slot is empty

The node address changed bit is set when the node address switch
setting has been changed since power up. The new node address does
not take affect until the adapter has been powered down and then
powered back up.