Rockwell Automation 1794-IE4XOE2,1794-IE8,1794-OE4,D17946.5.2 FLEX I/O ANALOG MODULE User Manual

Page 39

Advertising
background image

4–7

Configuring Your Module and Reading Status from Your Module with a Remote I/O Adapter

Publication 1794Ć6.5.2 - May 1996

Analog Output Module (1794-OE4/B) Write Configuration
Block

Word/Dec. Bit

15

14

13

12

11

10

09

08

07

06

05

04

03

02

01

00

Word/Octal Bit

17

16

15

14

13

12

11

10

07

06

05

04

03

02

01

00

Write Word 0

S

Analog Data - Channel 0

Word 1

S

Analog Data - Channel 1

Word 2

S

Analog Data - Channel 2

Word 3

S

Analog Data - Channel 3

Word 4

0

Not used - set to 0

M3 M2 M1 M0

Word 5

0

Not used - set to 0 C3

C2

C1

C0

Not used - set to 0

F3

F2

F1

F0

Word 6 thru 9

Not used - set to 0

Word 10

S

Safe State Value - Channel 0

Word 11

S

Safe State Value - Channel 1

Word 12

S

Safe State Value - Channel 2

Word 13

S

Safe State Value - Channel 3

Where:

S = Sign bit (in 2's complement)

M = Multiplex control

C = Configure select bit

F = Full range bit

Range Selection Bits for the 1794-OE4/B Analog Output Module
(Word 5)

Channel No.

Channel 0

Channel 1

Channel 2

Channel 3

F0

C0

F1

C1

F2

C2

F3

C3

Decimal Bits (Octal Bits)

00

08 (10)

01

09 (11)

02

10 (12)

03

11 (13)

4-20mA

0

1

0

1

0

1

0

1

0-10V dc/0-20mA

1

0

1

0

1

0

1

0

Ć10 to +10V dc

1

1

1

1

1

1

1

1

Off

1

0

0

0

0

0

0

0

0

C = Configure select bit
F = Full range bit

1

When configured to off, individual channels will send 0V or 0mV on Series B modules. On Series A modules, 2V or 4mA is output
until the module is configured.

Word/Bit Descriptions for the 1794-OE4/B Analog Output
Module Write

Word

Decimal Bit

(Octal Bit)

Definition

Write Word

0

Bits 00-14

(00-16)

Channel 0 analog data - 12Ćbit left justified two's complement number; unused

lower bits are zero; 4Ć20mA uses all 16 bits.

0

Bits 15 (17)

Channel 0 analog data sign bit.

Advertising