ControlNet Scanner Card

27

Publication 1784-5.35 – April 1999

Table B
ControlNet status interpretation

steady –

indicator is on continuously in the defined state.

alternating –

the two indicators alternate between the two defined states at the same time (applies to

both indicators viewed together). The two indicators are always in opposite states, out of phase.

flashing –

the indicator alternates between the two defined states (applies to each indicator viewed

independent of the other). If both indicators are flashing, they must flash together, in phase.

and

A

B

Cause:

Action:

off

no power

none or power up

steady red

faulted unit

cycle power or reset unit

If fault persists, contact your Rockwell
Automation representative or distributor.

alternating red/green

self-test

none

alternating red/off

incorrect node configuration

check network address and other
ControlNet configuration parameters

or

A

B

Cause:

Action:

off

channel disabled

program network for redundant media,
if required

steady green

normal operation

none

flashing green/off

temporary errors

none; unit will self-correct

la ing gr n o

node is not configured to go on line

make sure the configuration keeper node
is present and working ➀

flashing red/off

media fault

check media for broken cables, loose
connectors, missing terminators, etc.

no other nodes present on network

add other nodes to the network

flashing red/green

incorrect network configuration

cycle power or reset unit

If fault persists, contact your Rockwell
Automation representative or distributor.

➀ The configuration keeper node is the node responsible for distributing ControlNet configuration data to all nodes on the

network.

Important:

The LEDs do not apply to the network access port (NAP)
connection.