English section, Introduction, Wiring and safety guidelines – Rockwell Automation 2706-P42R_P42C_P43R_P43C_P44R_P44C_P72CNx_P74CNx InView Marquee Message Display User Manual
Page 2: Inview marquee message display
 
1
Publication 2706-IN006E-EN-P
Installation Instructions
English Section
InView Marquee Message Display
Introduction
These instructions show how to change the serial address and how to 
mount InView series signs with NEMA Types 4, 4X, and 12 enclosures. 
These signs are intended for indoor use only. Type 4 enclosures are 
intended to provide a degree of protection against windblown dust 
and rain, splashing water, and hose-directed water. Type 4X 
enclosures are intended to provide a degree of protection against 
corrosion, windblown dust and rain, splashing water, and 
hose-directed water. Type 12 enclosures are in a sealed case that is, 
dust free, gasketing, and spray down resistant.
Wiring and Safety 
Guidelines
Install the InView display conforming to NFPA 70E, Electrical Safety 
Requirements for Employee Workplaces. In addition to the NFPA 
general guidelines, refer to the following:
Careful cable routing helps minimize electrical noise. Route incoming 
power to the module by a separate path from the communication 
cables.
Do not run communications wiring and power wiring in the 
same conduit!
Where communication and wire paths must cross, make their 
intersection perpendicular.
Grounding helps limit the effects of noise due to electromagnetic 
interference (EMI). To avoid problems caused by EMI, properly 
ground all equipment and use shielded cables.
IMPORTANT
Power wiring must be in accordance with Class I, 
Class II and Class III Division 2 wiring methods 
(Articles 501-4(b), 502-4(b) and 503-3(b) of the 
National Electrical Code, NFPA70) and in 
accordance with the local authority having 
jurisdiction.