Devicenet connections – Rockwell Automation 2755 AdaptaScan Bar Code Readers User Manual

Page 51

Advertising
background image

Installing the Wiring Base and Power Supply

3–16

For network wiring, the wiring base has two DeviceNet terminal
blocks; one for incoming power and communications, the other for
outgoing power and communications. DeviceNet communications
requires 3 wires (2 communications, 1 ground) and a shield. You can
install the Reader in a single or multiple drop configuration. Up to 63
slave devices can be installed on a single DeviceNet master/slave
network. Up to 32 Readers can be installed on a DeviceNet
peer-to-peer network.

Reader

Other Devices

Reader

Reader

Both DeviceNet terminal blocks are tied to each other. You can
connect the wiring to either terminal block. Use cabling (Catalog
No. 1485C-P1A50, -P1A150 or -P1A300) for all DeviceNet
connections.

Line
Termination

V+

Can_H

Shield

Can_L

V-

V+

Can_H

Shield

Can_L

V-

See DeviceNet Cable System Planning and Installation Manual
(Publication No. 1485-6.7.1) for recommendations and cable
accessories.

Line Termination

The two devices furthest apart from each other on a DeviceNet
network must be terminated. A termination switch is provided.
Only the devices at the ends of the network can be terminated.

DeviceNet Connections