When the maximum programmed percentage of synchronous speed (set point) is
obtained, the field coil is energized on the falling pulse of the negative square
wave (i.e. a rising sinusoid) from the slip frequency generator. A fixed time period
after synchronization, the autoload signal is raised. The field coil is energized
only if the TRANSITION COMPLETE has been received.

Optional Equipment

Field Current Failure Relay
Load and Unload Auxiliary Contacts – The outputs are energized 2 sec.

after the field is applied and is maintained until the field is removed.

Display/Metering Features

The product in conjunction with the PanelView 300e Micro Terminal (PV) will
perform the following metering/display functions:

display all detected fault conditions
display the slip frequency and starting time during startup
display the power factor during run mode.
accept set points for the following:

maximum % asynchronous speed [% of synchronous speed]
power factor set point and trip delay
maximum allowable time at stalled state (maximum slip
maximum allowable time at 50% speed
maximum allowable time at synchronizing speed (typically at 95%

speed)

function order (allows adjustment of the slope of the acceleration/stall

time trip curve).

incomplete sequence timer trip delay
fault mask for PF transducer diagnostics

Refer to

Chapter 5

for complete details.

Squirrel-Cage Winding Protection

Protects the squirrel-cage winding from long acceleration and stall
conditions during starting.

Field Winding Application Control

The signal that triggers application of the field excitation when the
programmed asynchronous speed is obtained.

Incomplete Sequence Timing Relay

Trips the system if the overall starting time is exceeded.

Pull Out Protection

Monitors the lagging power factor during running to detect a loss of
synchronism

Field Voltage Failure Relay Input

Monitors the condition of the static exciter output. This relay must be
supplied by the customer if the SyncPro II is not supplied as a configured
unit within an Allen-Bradley motor controller.