Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

53

Chapter

6

Monitoring

Phase Angle/Power Factor

A key protection component of the SyncPro II is to monitor Power Factor.
Monitoring Power Factor is one of the most reliable methods to determine if a
motor is running properly. The SyncPro II system utilizes a Phase Angle
Transducer which provided a proportional signal to the measured phase angle
(angle difference between motor voltage and current).

The phase angle transducer board provides a 4...20mA output proportional to
-90...90º. The SyncPro II utilizes this input to calculated Power Factor.

To provide an accurate measurement the voltage and current inputs must be in
the proper relationship, V

ab

and I

c

.

Figure 30 - Voltage and Current Inputs Relationship

)

Cos

PF =

Va

Vb

Ic

Vab