Wiring guidelines, Figure 4 – Rockwell Automation 1902 Syncpro II User Manual

Page 24

Advertising
background image

26

Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

Chapter 3

Installation

Wiring Guidelines

The SyncPro II can accept either two- or three-wire control. The control chosen
will determine the configuration of the control hardware. Consider the following
two inputs and single output when selecting the type of control:

If using two-wire control, the two inputs (I:2/0 and I:2/1) are tied together.
They are both low in order to stop the SyncPro II (see

Summary on page 32

) and

both high in order to run the device. To start the device after a fault, the START
input (I:2/1) must be taken low and then closed again. In this configuration, the
RUN output acts as a run command (see

Figure 4

).

If using three-wire control, the NOT STOP input must be maintained high in
order to run the device. Momentarily opening this input will cause the SyncPro II
to stop (see

Summary on page 32

). Momentarily closing the START input will

start the SyncPro II (given that all permissives are satisfied). In this configuration,
the RUN output acts as a start command (see

Figure 5

).

Figure 4 - Two-wire Control

In both cases, the RUN output will follow the state of the START input,
provided that all starting conditions are met. Note that in all cases, stopping the
motor is done via the hardwired control circuit logic, and notification only is
given to the SyncPro II.

Figure 4

shows a typical two-wire control circuit. The selector switch is used to

control the NOT STOP and the START as a pair. It is also used to ensure the
motor is stopped via the hardwired control circuit logic, (even though in this case
the RUN output will be removed when the selector switch is turned off ).

I:2/0

NOT STOP input

I:2/1

START input

O:0/1

RUN output

Advertising