Set point 2: operating frequency, Set point 3: function number – Rockwell Automation 1902 Syncpro II User Manual
Page 40

42
Rockwell Automation Publication 1902-IN001B-EN-E - April 2013
Chapter 5
Programming SyncPro II
Set Point 2: Operating Frequency
This set point determines the operating system frequency. This allows the
SyncPro II to properly determine the appropriate minimum percent slip
frequency.
Figure 17 - Function Number
Set Point 3: Function Number
The function number entry determines the slope of the curve between the 50%
speed trip time and the 95% speed trip time – set point 4 and 5. Although the trip
time is set as 50% and 95% speed, the intermediate points between these values
can be shaped to cause the trips for 51% and 94% to occur more or less quickly
depending on which function number is selected. According to
, more
time is allowed when function 1 is selected, and less time is allowed when
function 5 is selected.