7 - troubleshooting, Last trip table, Chapter 7 – Rockwell Automation 1902 Syncpro II User Manual

Page 53: Troubleshooting, Chapter

Advertising
background image

Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

55

Chapter

7

Troubleshooting

Last Trip Table

To aid in troubleshooting, the unit stores the last 50 recorded faults. These can be
accessed by viewing the contents of the alarm history.

Table 5 - Troubleshooting Guide

Problem or Trip
Indicated

Indication of the following conditions Possible Solutions

Pullout trip (power factor)
[PULL OUT TRIP
(POWER FACTOR)]

• Motor overloaded
• Loss of DC excitation
• Static exciter DC current level set

too low

• Lessen the motor loading and/or

overload

• Repair static exciter
• Increase current setting on static

exciter if lagging

• Decrease current setting on static

exciter if leading

• Mask leading power factor trip if

application/ motor is designed for it

Squirrel-cage
Protection Trip
[SQUIRREL-CAGE
PROTECTION TRIP]

• Motor overloaded at start

• Remove or lessen load for start

Incomplete Start Sequence
Time Exceeded
[INCOMPLETE START
SEQUENCE TRIP]

• Motor overloaded at start
• Field contactor or FC pilot relay coil

failure

• Remove or lessen load for start
• Replace coil(s)

No Transducer Input
[POWER FACTOR XDCR –
NO INPUTS]

• The transducer is putting out less than

12 mA when the motor is off (should
be 12 mA)

• Check the wiring for the voltage

sensing on the transducer board.

• Replace phase angle transducer board

if necessary.

• Replace analog card in SyncPro II

chassis

CT Open/Shorted
[POWER FACTOR XDCR –
CT OPEN/SHORT]

• The CT is either open or shorted.

• Check the wiring between the CT and

the transducer board.

• Replace the CT if necessary.

CT Reversed
[POWER FACTOR XDCR–
CT REVERSED]

• The CT is incorrectly wired to the

transducer board.

• Reverse the leads of the CT at the

transducer board.

No Signal @ SLC
[POWER FACTOR XDCR–
NO SIGNAL AT PLC]

• There is no signal at the PLC analog

card from the PF transducer board.

• Check the wiring between the

transducer board and the PLC
analog card.

• Ensure that there is power to the

transducer board.

• Replace the PLC analog card or

transducer board as required.

Transducer Problem
[POWER FACTOR XDCR
CIRCUIT FAULT]

• The transducer is behaving

unpredictably.

• This is an all-encompassing fault and

could include anything from the CT, the
transducer board, or the PLC analog card

Advertising