7 - troubleshooting, Last trip table, Chapter 7 – Rockwell Automation 1902 Syncpro II User Manual

Page 53: Troubleshooting, Chapter

Advertising
background image

Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

55

Chapter

7

Troubleshooting

Last Trip Table

To aid in troubleshooting, the unit stores the last 50 recorded faults. These can be
accessed by viewing the contents of the alarm history.

Table 5 - Troubleshooting Guide

Problem or Trip
Indicated

Indication of the following conditions Possible Solutions

Pullout trip (power factor)
[PULL OUT TRIP
(POWER FACTOR)]

Motor overloaded
Loss of DC excitation
Static exciter DC current level set

too low

Lessen the motor loading and/or

overload

Repair static exciter
Increase current setting on static

exciter if lagging

Decrease current setting on static

exciter if leading

Mask leading power factor trip if

application/ motor is designed for it

Squirrel-cage
Protection Trip
[SQUIRREL-CAGE
PROTECTION TRIP]

Motor overloaded at start

Remove or lessen load for start

Incomplete Start Sequence
Time Exceeded
[INCOMPLETE START
SEQUENCE TRIP]

Motor overloaded at start
Field contactor or FC pilot relay coil

failure

Remove or lessen load for start
Replace coil(s)

No Transducer Input
[POWER FACTOR XDCR –
NO INPUTS]

The transducer is putting out less than

12 mA when the motor is off (should
be 12 mA)

Check the wiring for the voltage

sensing on the transducer board.

Replace phase angle transducer board

if necessary.

Replace analog card in SyncPro II

chassis

CT Open/Shorted
[POWER FACTOR XDCR –
CT OPEN/SHORT]

The CT is either open or shorted.

Check the wiring between the CT and

the transducer board.

Replace the CT if necessary.

CT Reversed
[POWER FACTOR XDCR–
CT REVERSED]

The CT is incorrectly wired to the

transducer board.

Reverse the leads of the CT at the

transducer board.

No Signal @ SLC
[POWER FACTOR XDCR–
NO SIGNAL AT PLC]

There is no signal at the PLC analog

card from the PF transducer board.

Check the wiring between the

transducer board and the PLC
analog card.

Ensure that there is power to the

transducer board.

Replace the PLC analog card or

transducer board as required.

Transducer Problem
[POWER FACTOR XDCR
CIRCUIT FAULT]

The transducer is behaving

unpredictably.

This is an all-encompassing fault and

could include anything from the CT, the
transducer board, or the PLC analog card

Advertising