Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

51

Programming SyncPro II

Chapter 5

Access Code

The Access Code Screen allows authorized users to log in to secured screens and
modify their own password. To log in, press the F1 key and enter your user ID
and password using the alphanumeric keypad that opens during a login request.
Login is successful if the “Logged in as:” indicator displays the correct username.

To change your password, press F3 and enter the current and new password to
make the change. If both passwords match, then it successfully changes. Press F2
key to log out in the end of the session. The “Logged in as:” indicator username
will disappear.

Figure 28 - Log In/Log Out

Prior to programming the unit a user must log in with full access writes. The
default administrator (admin) Access Code is “12345”. It is recommended this be
changed during product commissioning.

Settings

The Settings Screen provides access to PVc C400 built-in HMI configuration
screen and offers capability to set up SyncPro II relative time stamp. Please not
that the time stamp is reset when power is removed.

Figure 29 - Settings