Set point 7: incomplete sequence trip time delay, Set point 8: power factor trip – Rockwell Automation 1902 Syncpro II User Manual

Page 45

Advertising
background image

Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

47

Programming SyncPro II

Chapter 5

Set Point 4: Squirrel-Cage Protection Trip Time (at 95% speed)

Allowable Range: 5...80 seconds

Factory Default Setting: 5 s (5 seconds)

Set Point 5: Squirrel-Cage Protection Trip Time (at 50% speed)

Allowable Range: 2 s to Value in Set Point 4

Factory Default Setting: 2 s (2 seconds)

Set Point 6: Squirrel-Cage Protection Trip Time (at stall)

Allowable Range: 1 s to Value in Set Point 5

Factory Default Setting: 1 s (1 second)

Figure 21 - Incomplete Sequence Trip Time

Set Point 7: Incomplete Sequence Trip Time Delay

Allowable Range: 1...80 seconds

Factory Default Setting: 3 seconds

Set Point 8: Power Factor Trip

Allowable Range: 60...100 (% of unity)\

Factory Default Setting: 80 (0.8 lagging power factor)