Set point 7: incomplete sequence trip time delay, Set point 8: power factor trip – Rockwell Automation 1902 Syncpro II User Manual
Page 45
![background image](/manuals/580310/45/background.png)
Rockwell Automation Publication 1902-IN001B-EN-E - April 2013
47
Programming SyncPro II
Chapter 5
Set Point 4: Squirrel-Cage Protection Trip Time (at 95% speed)
Allowable Range: 5...80 seconds
Factory Default Setting: 5 s (5 seconds)
Set Point 5: Squirrel-Cage Protection Trip Time (at 50% speed)
Allowable Range: 2 s to Value in Set Point 4
Factory Default Setting: 2 s (2 seconds)
Set Point 6: Squirrel-Cage Protection Trip Time (at stall)
Allowable Range: 1 s to Value in Set Point 5
Factory Default Setting: 1 s (1 second)
Figure 21 - Incomplete Sequence Trip Time
Set Point 7: Incomplete Sequence Trip Time Delay
Allowable Range: 1...80 seconds
Factory Default Setting: 3 seconds
Set Point 8: Power Factor Trip
Allowable Range: 60...100 (% of unity)\
Factory Default Setting: 80 (0.8 lagging power factor)