Specifications, General, For phase angle transducer – Rockwell Automation 1902 Syncpro II User Manual

Page 17: Pvc c400 specifications, Micrologix 1500 specifications, General for phase angle transducer

Advertising
background image

Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

17

Product Description

Chapter 1

Specifications

General

For Phase Angle Transducer

PVc C400 Specifications

See Publication

2711C-IN001_-EN-P

, pages 30...31.

MicroLogix 1500
Specifications

See Publication

1764-UM001_-EN-P

, Appendix A.

Operating Power

Input Line Voltage

120V AC, 50/60 Hz

Input Current

0...5 A

Temperature and Humidity

Temperature
(Maximum Ambient)

Operating: 0...40ºC (32...104ºF)

Storage: -20...65ºC (-4...149ºF)

Humidity

5...95% (non-condensing)
Maximum temperature: 40 ºC (104 ºF)

General

Accuracy

3% span

Housing

Flame retardant plastic case

Weight

2.4 kg maximum

Climate

Storage

-20...70 ºC (-4...158 ºF)

Temperature range

Operational at 0...60 ºC (32...140 ºF)
Calibrated at 23 ºC (73 ºF)

Humidity

Up to 95% relative humidity, non-condensing

Input

Frequency

50/60 Hz

Current

0.2...10 A

Range (A)

20...120%

Burden

5 VA maximum

Voltage

115...230V, ±10%

Range (V)

±20% (20...120% with separate auxiliary)
Burden 1 VA maximum

Overload Capacity

Six times rated current for 30 s

1.25 rated voltage for 10 s

Electrical Tests

Dielectric Test

2 kV RMS per BS 5458

Impulse Test

5 kV transient as BEAMA 219 and BS 923

Surge Withstand

ANSI C37-90A

Certification

CSA Approved