Programming SyncPro II
Chapter 5
Set Point 10: Diagnostic Fault Mask
This parameter/screens are used to define a fault mask code that will disable
individual diagnostic faults. The value is based on the 16 bit Fault Mask Word.
Please refer to Edit Set Points section for additional information.
Table 3 - Mask Description
Edit Set Points
Figure 18 - Minimum Slip Frequency
Set Point 1: Minimum % Synchronous Slip Frequency
Allowable Range: 2...10% (slip at which synchronization will occur as a
percentage of synchronous speed)
Factory Default setting: 5% (95% speed)
Typically set at: 5%
Code
Mask Description
0
Enable All Faults
272
Mask Commissioning Faults
2000
Mask All Power Factor Faults
1984
Mask Power Factor Transducer Circuit Faults
64
Mask Power Factor Transducer No Input Fault
128
Mask Power Factor Transducer CT Open/Shorted Fault
256
Mask Power Factor Transducer CT Input Reversed Fault
512
Mask Power Factor Transducer No Signal at PLC Fault
1024
Mask Power Factor Transducer Abnormal Operation Fault
16
Mask PLC Reversed Power Factor Fault