Rockwell Automation Publication 1902-IN001B-EN-E - April 2013

45

Programming SyncPro II

Chapter 5

Set Point 10: Diagnostic Fault Mask

This parameter/screens are used to define a fault mask code that will disable
individual diagnostic faults. The value is based on the 16 bit Fault Mask Word.
Please refer to Edit Set Points section for additional information.

Table 3 - Mask Description

Edit Set Points

Figure 18 - Minimum Slip Frequency

Set Point 1: Minimum % Synchronous Slip Frequency

Allowable Range: 2...10% (slip at which synchronization will occur as a
percentage of synchronous speed)

Factory Default setting: 5% (95% speed)

Typically set at: 5%

Code

Mask Description

0

Enable All Faults

272

Mask Commissioning Faults

2000

Mask All Power Factor Faults

1984

Mask Power Factor Transducer Circuit Faults

64

Mask Power Factor Transducer No Input Fault

128

Mask Power Factor Transducer CT Open/Shorted Fault

256

Mask Power Factor Transducer CT Input Reversed Fault

512

Mask Power Factor Transducer No Signal at PLC Fault

1024

Mask Power Factor Transducer Abnormal Operation Fault

16

Mask PLC Reversed Power Factor Fault