3Ć4

3.4

OnĆBoard Battery Replacement

WARNING

THE BATTERY USED WITH THIS DEVICE MAY PRESENT A HAZARD IF

MISTREATED. DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100_C

(212_F), INCINERATE, OR SWALLOW. REPLACE BATTERY WITH RELIANCE

ELECTRIC M/N 57C385 ONLY. DISPOSE OF USED BATTERY PROMPTLY. FAILURE

TO

OBSERVE

THIS

PRECAUTION

COULD

RESULT

IN

BODILY

INJURY.

See section 5.2 for a list of the possible reasons that the BAT. OK"

light on the Processor faceplate can shut off. If you need to replace

the battery, the superĆcapacitor will provide a typical 10 hours of

backĆup power between the time the BAT. OK" light goes off and

power is removed from the rack, and the time you insert and activate

the new battery. If you replace the battery within this time limit, you

will not need to reĆload the operating system and application tasks.

Complete battery specifications can be found in Appendix A.
Usethefollowing procedureto replacethebattery on theProcessor

module.
Step 1.

Turn off power to the system. All power to the rack, as well

as all power to the wiring leading to the module, should be

off.

Step 2.

Use a screwdriver to loosen the screws holding the

connectors to the module. Remove the connectors from

themodule.

Step 3.

Loosen thescrews that hold themodulein therack.

Removethemodulefrom theslot in therack, being careful

not to touch theconnectors on theback of themodule.

Step 4.

Take the old battery out of the holder. Remove the tape

from the new battery and insert it in the holder. Make

certain that the battery is facing the proper direction.

Step 5.

ReĆinsert themoduleinto thecorrect slot in therack. Usea

screwdriver to securethemoduleinto theslot.

Step 6.

ReĆattach the connector(s) to the mating half on the

module. Make certain that the connector is the proper one

for this module. Use a screwdriver to secure the connector

to themodule.

Step 7.

Turn on power to therack. Themodulewill automatically

execute its powerĆup diagnostics. The green OK" light

should belit, and theBAT. OK" should belit. If this

Processor or any Processor in the rack displays code

LO", you will need to reĆload the operating system. See

4.1 for moreinformation.