5 incorrect data – Rockwell Automation 57C435 Processor Module, AutoMax User Manual

Page 33

Advertising
background image

5Ć7

5.5

Incorrect Data

Problem: The data used by application tasks is either always off,

always on, or different than expected. The possible causes of this are

thefollowing: a modulein thewrong slot, a programming error, or a

malfunctioning module.
Step 1.

Verify that all inputs to the rack are wired to the correct

devices.
Confirm that all connections at the terminal strip are tight.

Connect a voltmeter to the proper points on the terminal

strip and toggle each device. Verify that the device is

generating the correct voltage or current, depending upon

themoduleyou aretesting. If thevoltageor current is

incorrect, there is a problem with the external device, its

power supply, or thewiring to theterminal strip.
Check the cable for continuity between the faceplate

connector and the terminal strip.

Step 2.

Verify that the input circuit on each input module is

working correctly.
Toggle the input devices to verify that the LED associated

with each is also toggling. If it is not toggling, either the

LED or theinput moduleitself is malfunctioning.

Step 3.

Verify that each module can be accessed.
Connect the personal computer to the rack and run the

ReSource AutoMax Programming Executive.
Stop all programs that may berunning.
UsetheI/O Monitor function to display theindividual I/O

points or registers on the module, whichever is

appropriate. If thepoints can bemonitored, theproblem

lies in the application software (refer to steps 4 and 5). If

thepoints cannot bemonitored, theproblem lies in the

software(go on to step 6).

Step 4.

For all modules in the rack, verify that the configuration

references the correct slot and register locations. For

remote I/O installations, also verify that the master slot and

drop number are referenced correctly.

Step 5.

Verify that the application programs running in the rack

arecorrect.
Check to see that the application programs that reference

thesymbolic names associated with thehardwarein the

rack have declared those names COMMON.

Step 6.

Verify that the hardware is working correctly.
To test local I/O, systematically swap out the module in

question and the Processor module(s). If the problem

persists, take all of the modules except the module in

question and oneProcessor out of therack. If theproblem

is now corrected, one of the other modules in the rack is

causing the problem. Reconnect the other modules one at

a time until the problem reappears. If none of these tests

reveals the problem, replace the backplane.
To test the remote I/O system, first verify that the remote

I/O system is communicating with the drop that contains

the module being tested. Next, by systematically

Advertising
This manual is related to the following products: