4Ć1

4.0 PROGRAMMING

For information about programming, seetheAutoMax language

instruction manuals and theAutoMax Executiveinstruction manual

referenced in 1.1.
The remainder of this section describes how to load the operating

system, or runbase, onto the Processor(s) in the rack and how to

access theavailableProcessor ports through application tasks. Note

that you cannot load a Version 1.0 runbase on a 57C430A or M/N

57C431 Processor module. You must load the runbase from the

Version 2.0 or Version 3.0 Programming Executive software. The M/N

57C435 Processor requires the runbase from the Version 3.1 or later

Programming Executivesoftware. You will not beableto load the

operating system using an earlier version of the Programming

Executive software.

4.1

Loading the Operating System

Beforeyou can go onĆlineto any rack in thesystem, theoperating

system, or runbase, for the AutoMax Processor module(s) must be

loaded to the local rack from the personal computer on which you

haveinstalled theAutoMax Executivesoftware. Theoperating

system, which oversees the operation of the CPU and the execution

of application tasks, is provided in three versions: 6010/6011 Ć

Standard, 6010/6011 Ć Ethernet, and 7010 Ć Standard. The 6010/6011

Ć Standard or 6010/6011 Ć Ethernet operating system can be used

with M/N 57C430A or M/N 57C431 Processors. In order to use the

Ethernet functions that allow communication over Ethernet using the

TCP/IP protocol, an Ethernet Network Interface module (M/N

47C440) must be installed in the rack and the Ethernet operating

system must be used. The Ethernet operating system is also required

if any of thefollowing functions areused in BASIC tasks:

READVAR%, WRITEVAR%, FINDVAR!, and CONVERT%. The7010 Ć

Standard operating system, which supports all of the Ethernet

functions, must beused with theM/N 57C435 Processor.
When you load the operating system to the Processor modules in the

rack, you will be prompted for which operating system you want to

load for theM/N 57C430A and M/N 57C431 Processors. The7010 Ć

Standard operating system will be loaded onto all M/N 57C435

Processors. Notethat if you haveloaded the6010/6011 Ć Standard

operating system and then you use the Ethernet functions in an

application task, the Processor will display error code 4A on its LEDs

when you try to put the task into run.
The 6010/6011 Ć Ethernet operating system will occupy

approximately 121K or RAM, leaving 135K available for application

tasks on theM/N 57C430A Processor. The6010/6011 Ć Standard

operating system will occupy approximately 106K or RAM, leaving

150K availablefor application tasks on theM/N 57C430A Processor.

The M/N 57C431 Processor makes 300K available for application

tasks, regardless of which operating system is used. The M/N

57C435 Processor also makes 300K available for application tasks.
The operating system(s) will be loaded at the maximum baud rate

available for the Processors being used. If you are using 6010/6011

and 7010 Processors in thesamerack, makesuretheleftĆmost

Processor is a 7010 (M/N 57C435) Processor. This will allow the

operating systems to be loaded at 19200 baud. If the leftmost