5Ć8

swapping out modules, determine whether the module

being tested is the only module that is not working

correctly. If morethan onemoduleis not working correctly,

the problem most likely lies in the remote I/O system.

Refer to the instruction manual for the M/N 57C416

RemoteI/O Communications modulefor moreinformation.

If theproblem does not liein theremoteI/O system, it

probably involves the remote rack.
To test the remote rack, systematically swap out the

module being tested and the slave Remote I/O module. If

the problem persists, take all of the modules except the

slaveRemoteI/O moduleand themodulebeing tested out

of the rack. If the problem is now corrected, one of the

other modules in the rack is malfunctioning. ReĆconnect

theother modules oneat a timeuntil theproblem

reappears. If the problem appears to be neither in the

remote I/O system nor in the remote rack replace the

backplane.