3 bus error – Rockwell Automation 57C435 Processor Module, AutoMax User Manual

Page 29

Advertising
background image

5Ć3

on thebattery holder. If noneof theaboveactions correct the

problem, replace the battery.

5.3

BUS ERROR

Problem: Codes 31" or 50" through 58" appear on the Processor

module's LEDs. These codes signify that a bus error occurred when

the system attempted to access an I/O module. The possible causes

of this error arethefollowing: a missing module, a modulein the

wrong slot, or a malfunctioning module. It is also possible that the

user has attempted to write to the wrong registers on a module

through an application task. Usethefollowing procedureto isolatea

bus error:
Step 1.

Determine where the bus error occurred.
Connect the personal computer to the rack and run the

ReSource AutoMax Programming Executive. Display the

error log for the Processor that indicates the error. The

error log should indicate the address that caused the bus

error or a line number in a BASIC or Control Block

application task. Theaddress will bedisplayed in

hexadecimal notation. To decode the address, follow the

directions below.
a. To determine the slot number where the bus error

occurred, convert the hex address into a bit pattern

and decode in decimal notation as follows:

Most Significant 16 Bits

31 30 29 28 27 26 25 24

22 21 20 19 18 17 16

23

0

0

0

0

1

0

BYTE

BIT #

THIS RACK

SLOT #

0 = Forced

1 = Unforced

BIT