EĆ1

Appendix E

Run Time LED Error Codes

WARNING

ONLY QUALIFIED PERSONNEL FAMILIAR WITH THE CONSTRUCTION AND

OPERATION OF THE CONTROLLED EQUIPMENT SHOULD INSTALL, ADJUST,

OPERATE, OR SERVICE THIS EQUIPMENT. READ AND UNDERSTAND THIS

MANUAL AND OTHER MANUALS APPLICABLE TO YOUR INSTALLATION.

FAILURE TO OBSERVE THIS PRECAUTION COULD RESULT IN BODILY INJURY.

WARNING

INSERTING OR REMOVING THIS MODULE OR ITS CONNECTING CABLES MAY

RESULT IN UNEXPECTED MACHINE MOTION. POWER TO THE MACHINE

SHOULD BE TURNED OFF BEFORE INSERTING OR REMOVING THE MODULE

OR ITS CONNECTING CABLES. FAILURE TO OBSERVE THESE PRECAUTIONS

COULD RESULT IN BODILY INJURY.

STOP ALL Error Codes

Thefollowing hardwareand softwareerror codes causeall tasks running in the

rack to stop.
10

Event count underflow

Ć too many WAITs (max. 32768)

Ć not enough SETs (BASIC tasks)

11

Event count overflow

Ć too many SETs (max. 32767)

Ć not enough WAITs (BASIC tasks)

12

Hardware event timeĆout

Ć interrupt time exceeded programmed timeĆout

limit in a Control Block task

13

Runbaseboot error

Ć a check on therunbasefailed

14

Processor overlap limit exceeded

Ć ran out of processing capacity (time)

15

External watchdog timeĆout detected

Ć another processor in the same rack stopped

17

Address error detected

Ć caused by a read/write to an invalid address

18

Spurious interrupt or hardware failure

19

Power failure detected

1A

Watchdog on this Processor failed

1b

Hardware event count limit exceeded

Ć too many interrupts set without being

acknowledged

Ć program too long

Ć collective scans too fast

1C

Illegal instruction detected

Ć runbasesoftwarefault

Ć bad Processor module

Ć bad EPROMs