Rockwell Automation 57C435 Processor Module, AutoMax User Manual

Page 31

Advertising
background image

5Ć5

A Modbus InterfaceModule(M/N 57C414)

Least Significant 16 Bits

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

BIT

R

b

where R is a local register address, which may be used with the I/O monitor.

Determine the Modbus register number from the following table:

R (Decimal)

Modbus Register (Decimal)

ăă64ă-ă319

ă320ă-ă575

ă576ă-ă1599

1600ă-ă2623

[(R - 64)*16] + BYTE BIT # + 8*b + 1

[(R - 320)*16] + BYTE BIT # + 8*b + 10001

(R - 576) + 30001

(R - 1600) + 40001

An AllenĆBradley Interface Module (M/N 57C418)

Least Significant 16 Bits

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

BIT

R

b

where R is a local register address, which may be used with the I/O monitor.

Determine the AĆB register number from the following table:

R (Decimal)

AĆB Register

(Decimal)

ăă64ă-ă319

ă320ă-ă575

ă576ă-ă1599

1600ă-ă2623

R - 64

R - 320

R - 576

R - 1600

AĆB

File

B0

B1

N0

N1

An AutoMateInterfaceModule(M/N 57C417)

Least Significant 16 Bits

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

BIT

R

b

where R is a local register address, which may be used with the I/O monitor.

Determine the AutoMate register number from the following table:

R (Decimal)

AutoMate Register (Octal)

ăă64ă-ă319

ă320ă-ă575

ă576ă-ă1599

1600ă-ă2623

0000.00 - 0377.17

0400.00 - 0777.17

ăăĂ2000 - 3777

ăăĂ4000 - 5777