EĆ3

Corrective action: correct the problem in application software. Error code 47 can

be caused by performing a PUT on a closed port. Error code 4A can be caused

by attempting to use Ethernet functions with the standard operating system

loaded. To use Ethernet functions, you must load the Ethernet operating system.

Multibus and Processor Bus STOP ALL Error Codes

50

Onboard parity error

51Ć54

Onboard bus error or access violation

55

Multibus parity error during read access

56Ć58

Multibus access violation or bus error

60

Network interrupt allocation failed

61

Network receiving queue overflow

62

Network transmit queue underflow

Corrective action: reset by cycling power and reĆloading configuration and

application tasks. If the small green LED labeled OK" on the Processor module

faceplate is off, replace the Processor module. Correct any incorrect accesses in

application software. Systematically swap out hardware modules. For error codes

55Ć58, if noneof theabovecorrect theproblem, try replacing thebackplane.

DriveĆRelated Error Codes

The following error codes indicate a power circuit or external drive system fault.

After correcting the problem, reset the Processor module to clear the error code.
80

Instantaneous overcurrent fault

Ć armature current exceeded IOC_THRESH value in CML task

81

Linesync loss fault

82

Tach loss fault

Ć 40% armature voltage with less than 5% tach feedback

83

Overspeed/overvoltage fault

Ć CML task OSV_FDBK exceeded OSV_THRESH number

84

Hardware overspeed fault

Ć drive analog module potentiometer setting exceeded

by input voltage

85

External IET fault

Ć external fault input triggered

86

Phaserotation fault

Ć incorrect phasing

87

Shorted SCR detected in power module

Corrective action: troubleshoot power circuit and external drive system.

Configuration Error Codes

The following error codes usually indicate a discrepancy between the actual

hardwareconfiguration and theI/O definitions in theconfiguration for therack.
E0

TASK specified in configuration uninstalled,

at wrong priority, of wrong type, on wrong

Processor module; wrong spelling of TASK

E1

Invalid configuration, configuration not successfully downloaded.

E2

I/O referenced in configuration is missing.

E3

I/O referenced in configuration is missing. Invalid configuration,

configuration not successfully downloaded.

E4

Error building task, insufficient memory in Processor Module.

Invalid configuration, configuration not successfully dovvnloaded.