Fatal errors, Informational messages – Rockwell Automation 57C435 Processor Module, AutoMax User Manual

Page 52

Advertising
background image

EĆ4

E5

Error building task, insufficient memory in Processor

Module. Invalid configuration, configuration not

successfully downloaded.

E6

I/O referenced in configurations is missing. Error building

task, insufficient memory in Processor Module.

E7

Invalid configuration, configuration not successfully

downloaded. I/O referenced in configuration is missing.

Invalid configuration, configuration not successfully

downloaded.

E8

Error installing application task, common symbol could not

be resolved, insufficient memory in Processor Module.

E9

Error installing application task, common symbol could not

be resolved, insufficient memory in Processor Module.

Invalid configuration, configuration not successfully

downloaded.

EA

Error installing application task, common symbol could not

be resolved, insufficient memory in Processor Module. I/O

referenced in configuration is missing.

Eb

Error installing application task, common symbol could not

be resolved, insufficient memory in Processor Module. I/O

referenced in configuration is missing. Invalid

configuration, configuration not successfully downloaded.

EC

Error building task; and error installing application task,

common symbol could not be resolved, insufficient

memory in Processor Module.

Ed

Error building task; and error installing application task,

common symbol could not be resolved, insufficient

memory in Processor Module. Invalid configuration not

successfully downloaded.

EE

Error building task; and error installing application task,

common symbol could not be resolved, insufficient

memory in Processor Module. I/O referenced in

configuration is missing.

EF

Common variable forced by another Processor Module.

Corrective action: verify that the configuration correctly describes the physical

configuration of the system and the tasks installed on the Processor module(s).

Reset by cycling power and reĆloading the configuration and application tasks.

For error codeEF, unĆforcethevariableand do a STOP ALL from theAutoMax

ON LINE PROGRAMMING menu.

Fatal Errors

Thefollowing error codes usually indicatethat therunbaseis not functioning

correctly. If any of these error codes appears, the configuration task and all

application tasks are deleted from the Processor module.
F0ĆF9

Fatal error

FAĆFF

Fatal error

Corrective action: cycle power. ReĆload the configuration task and all application

tasks. Replace the Processor module.

Informational Messages

The following codes signify a particular condition, not necessarily an error.
dd

This Processor module has successfully

completed powerĆup diagnostics and is waiting for

other Processor modules to complete their

diagnostics