background image

DĆ2

6.4.

Serial port fatal error

6.5.

Illegal interrupt on lower port of processor

6.6.

Transmit interrupt error

6.7.

Runbaseintegrity lost

6.8.

Bad runbasechecksum

6.9.

Transmit buffer error

7.0.

MultiĆprocessor runbase download in progress

7.1.

Disconnect timeĆout during download

7.2.

Spurious interrupt received

Corrective action: 6.3. may be caused by attempting AutoMax ONĆLINE

PROGRAMMING functions beforetherunbaseis loaded onto theProcessor

module(s) in the rack. In this case, exit the ONĆLINE PROGRAMMING menu and

download the runbase. 7.0 is a status message only. For all other error codes,

cyclepower and try to load therunbaseagain.

Loading the Runbase over the Network

8.0.

Bad message length specified for network message

8.1.

Bad destination drop

8.2.

Transmitting drop inactive

8.3.

Destination port unallocated

8.4.

Destination port busy

8.5.

Did not receive expected response

8.6.

Spurious network interrupt received

8.7.

Network message is being transmitted

Corrective action: 8.0. and 8.1. are caused by a failed Processor in the leftmost

slot. For 8.2., check the coax cable; then try replacing the network module. For

8.3. Ć 8.5., check the destination Network module, then the leftmost Processor in

thedestination rack. For 8.6. and 8.7., cyclepower and try to load therunbase

again.
Miscellaneous Process Errors
8.8.

Processor failure

Corrective action: replace Processor module.