18Ć24

for each port on the PMI Processors associated with the

selected UDC module (A and B).

Step 3.

Enter U" to select the UDC analog outputs, A" to select

the PMIĆA analog outputs, or B" to select the PMIĆB

analog outputs.

Step 4.

Enter the port (1Ć4) you want to configure.

Step 5.

If you entered U" (UDC) above, enter the task name (for

LOCAL variable), the variable name or register and bit

number of the variable you want to assign to the selected

UDC meter port.
If you selected A" (PMIĆA) or B" (PMIĆB), select the

parameter you want to assign to the port. Use the Up

Arrow and Down Arrow keys to scroll through the list of

available parameters displayed on the screen.

Step 6.

Enter a minimum and maximum value for the selected

variable in the Val @ -10V" and Val @ +10V" fields,

respectively.

Step 7.

When you are finished setting up the UDC and PMI meter

ports, press <ESC> to return to the Monitor menu.