Rockwell Automation 47C626 AutoMax Programming Executive V4.2 User Manual

Page 69

Advertising
background image

5Ć35

Figure 5.22 Ć Transferring a Rack Using TransferĆPlus

5.3.12

Importing a Rack from

AutoMax Version 1 or Version 2

You can import the configuration information and application tasks

for an AutoMax Version 1 or AutoMax Version 2 rack and any Remote

I/O racks into AutoMax Executive V4.x. The rack name must not

already exist in the selected system. If you want to use tasks

created with earlier versions of the AutoMax V3 Executive in a

V4.x environment, refer to section 1.4.5.
Before importing an AutoMax V1 rack, you must edit any Control

Block tasks as follows: decimal points must be added to any real

literal values that do not already have them. Blocks that allow real

literal values include the following: DIFF_LAG, INTEGRATE, LAG,

LEAD_LAG, PROP_INT, and PID. After adding the decimal points

where appropriate, the task must be reĆcompiled. No changes are

required for tasks in AutoMax V2 racks.
It is helpful to try to create a test rack in V4.x first to understand the

structure by which the configuration task and application tasks will be

organized when they are imported into V4.x. The Import command

will not delete the original files or alter them in any way.
If your system has .NET files, you must run NETIN to compile the

.NET files and generate a networkĆwide database prior to importing

AutoMax V2 racks. Refer to Appendix F for the NETIN procedure.
The Import procedure will add the variables and their descriptions

from the AutoMax configuration task to the rack's variable database.

The task names, types, priorities, critical flags, and Processor slots

from the configuration task TASK statements are added to the task

database.

Advertising