5Ć13

5.1.9.2

Generic Modules
A generic" module, identified by the prefix GEN", is added to the

appropriate slot in the local rack when IODEF statements are the only

statements found for the slot in the configuration task. The generic

module is used because the IODEF statement does not provide

enough information to determine the specific type of module used.

Note also that for a remote I/O network, no hardware is added to the

rack database for the same reason.

5.1.9.3

Accessibility of Variables Added by Import
Although the Remote I/O hardware which was configured in the

configuration task does not get added to the rack, all variables

defined for it are added to the rack's database. In the local (master)

rack, the variables defined for the corresponding slot will be mapped

to a generic module. Remote I/O variables are not accessible to the

user until the correct module or rail is actually added to the Remote

rack or Head through the Rack Configurator.
Variables that exist in the rack database, but are not attached to any

module at all, are called floating variables. These variables must be

either deleted from the databases or the correct modules added to

account for them and to properly document your application. Note

carefully that when you configure the remote I/O network hardware in

the Rack Configurator after the import procedure, you must be

careful to add the correct hardware (proper size rack or Remote

Head) the first time. This is important because if you make a mistake

and add the wrong hardware, the only method of modifying the

configuration is to remove the rack or Head and add the correct rack

or Head. However, removing the rack or Head will also delete all of

the floating variables that are mapped to the remote I/O system.

When you configure the remote I/O system, you will be prompted

that variables have already been configured for the hardware.
If floating variables exist in a remote I/O network when the

configuration object file is generated in the Task Manager, they will be

included in the configuration object code even though they are not

accessible in the Variable Configurator. Floating variables in the

master rack are flagged as errors. You can compile tasks when there

are floating variables in a remote I/O network. You cannot, however,

compile tasks when there are floating variables in a master rack.
Local network variables will be linked to networkĆwide names

whenever possible. If there is a networkĆwide name for the network

point used by a variable, the networkĆwide variable is linked to that

variable. Any network or remote I/O registers/ points configured as

both single and double integers will not import correctly. The

procedure will result in prompts that indicate duplicate Multibus

addresses" and will require you to delete the offending variables.

5.1.9.4

Register Assignments on Modules Added by Import
Registers defined for some modules in AutoMax V2 cannot be

configured in AutoMax Executive V4.x and will cause an error

message to be displayed (invalid/incompatible data type) when you

try to configure the module if you import the system or rack without

first checking your AutoMax V2 configuration. Refer to Appendix I for

examples.
Also, you can not define single and double integers in the same

addresses (except for generic cards in both local and remote racks,