MP-Series Electric Cylinders 27

Rockwell Automation Publication MPAR-IN001D-EN-P - September 2012

Tune Your Electric Cylinder

with RSLogix 5000 Software

This section shows the steps to tune electric cylinders with RSLogix 5000 software, version 16:

Tuning your electric cylinder requires you to calculate and configure the loop gain based
on the actual measured inertia.

By setting travel limits, your application minimum deceleration is defined.

Follow these steps to tune your electric cylinder.

1.

In the Axis Properties dialog box, click the Fault Actions tab.

2.

Click Set Custom Stop Action.

3.

In the Custom Stop Action Attributes dialog box, set the Brake Engage and the Brake
Release delay times to the values listed in

Specifications

on

page 42

.

4.

Reduce the default Stopping Time Limit from 10 seconds to 0.5 seconds.

TIP

These parameter settings work best if the electric cylinder is installed in a horizontal
(table top) or a wall mount (vertical) orientation.

IMPORTANT

To prevent the rod from moving or falling when installed in a vertical orientation, the
Stopping Time Limit must be set to 0.99 seconds or less.