32 MP-Series Electric Cylinders

Rockwell Automation Publication MPAR-IN001D-EN-P - September 2012

Configure the Kinetix 300 Drive for Electric Cylinders

These steps assume that an electric cylinder and the Kinetix 300 drive are installed and wired as
one axis of a motion system.

For help using the Kinetix 300 drive as it applies to setting up your electric cylinder, refer to

Additional Resources

on

page 47

. This procedure assumes that you are familiar with the Kinetix

300 drive.

1.

Run MotionView Onboard software.

2.

From the Drive Organizer, click Motor.

3.

Verify that your electric cylinder model is displayed in the Motor Model field.

4.

Click Change Motor.

The motor model will automatically update to the correct model number.

5.

Click Yes twice.

6.

Verify the motor model matches the electric cylinder model connected to the drive

7.

Click OK.

8.

From the Drive Organizer, click General.

9.

Using values from the following table, enter Accel Limit, Decel Limit, and User Units.

User Units can be entered in rev/mm or rev/in. Your choice determines the unit of
measure for the axis.

10.

From the Drive Organizer, click Homing.

Cat. No.

Accel/Decel Limits
rpm/s

User Units
rev/mm (rev/in.)

MPAR-x1xxxB-Vxx

120000

0.33333 (8.46667)

MPAR-x1xxxE-Vxx

36000

0.10000 (2.54000)

MPAR-x2xxxC-Vxx

72000

0.20000 (5.08000)

MPAR-x2xxxF-Vxx

28346

0.07874 (2.00000)

MPAR-x3xxxE-Mxx

36000

0.10000 (2.54000)

MPAR-x3xxxH-Mxx

18000

0.05000 (1.27000)