10

Setting

Example:
Required function:

Protective operation with
manual start, with muting,
4 muting sensors, max. 30 s
muting time.
Setting:
Upper switches set to "5" for
both processors
Lower switches set to "2" for
both processors

The function setting of MSR22LM is made by 4 rotational switches behind
the frontplate (see picture). The switches on the left make the setting for
μprocessor 1 (LED run 1) and the switches on the right for μprocessor (LED
run 2). For both processors the same functions must be set. On the upper
switches (1) the main function is adjusted. On the lower switches (10) the
setting of the muting time (Protective operation) or the number of steps
(stepping operation) is adjustable.
On muting or stepping function the light curtains LC 2 and LC 3 are always in
protective operation with manual start.

Protective operation without muting

0

3

6

9

0

3

6

9

0

3

6

9

0

3

6

9

ch1

ch2

10

1

M8015

Ansicht innen

Protective operation with muting

Indicators

Lower green LEDs
K1, K2:

-

On, when K1 and K2 are energized

Upper yellow LED
run 1:

-

Permanent on, when relay K1 and K2 are

energized

-

Flashes with 1 Hz when the unit waits for the

start signal after fault free operation (power up

of the unit)

-

Flashes fast with approx. 3 Hz when the start

button is pressed and all conditions for an

override are fulfi lled during muting

-

Flashes fast with approx. 3 Hz when at stepping

operation the unit waits for interruption of the

light

curtain

-

Flashes with failure code to indicate normal

indication states that disable the energisation

of the output relays (e.g. after not allowed

interruption of the light curtain) until the start

button is pressed

-

Flashes with failure code to indicate

special failures (e.g. undervoltage)

Semiconductor output 48:
-

Off , when unit is on special failure mode

-

Normally

off when relays K1 and K2 are

energized

-

Continuously on, when unit in muting mode

-

Shows the same failure codes as LED

run 1 (except on special failures)

Upper yellow LED run 2:

-

Permanent on, when unit operates correctly

-

Flashes with failure code to indicate special

operation failures (e.g. undervoltage)

Semiconductor output 58: - Off , when unit is on special failure mode
-

Off , when relays K1 and K2 are energized

-

Symmetric

fl ashing, when a normal functional

state is active that disables the energisation of

the output relays (e.g. not allowed interruption

of a light curtain)

-

Permanent on, when waiting for start

Switch 10: Start mode and feedback input

0

1

2

3

4

5

6

7

8

9

without feedback

input

with feedback input

S

wit

ch 1

0 LC 1

LC 2
LC 3

Auto
Manu
Manu

Auto
Auto
Manu

Auto
Auto
Auto

not

allowed

(fault 5)

Auto
Manu
Manu

Auto
Auto
Manu

Auto
Auto
Auto

not

allowed

(fault 5)

1 LC 1

LC 2
LC 3

Manu
Manu
Manu

Manu
Auto
Manu

Manu
Auto
Auto

Manu
Manu
Manu

Manu
Auto
Manu

Manu
Auto
Auto

Switch 10:

a = maximum muting time

b = maximum synchronising time

0

1

2

3

4

5

6

7

8

9

S

wit

ch 1

2

LC S1 Auto,
muting 2 sensors

a: 10 s / b: 3 s

a: 20 s / b: 3 s

a: 30 s / b: 3 s

a: 1 min / b: 6 s

a: 5 min / b: 30 s

a: 15 min / b: 90 s

a: 30 min / b: 3 min

a: 1 h / b: 3 min

a: 8 h / b: 3 min

no muting time monit

oring

3

LC S1 Manu,
muting 2 sensors

4

LC S1 Auto,
muting 4 sensors

5

LC S1 Manu,
Muting 4 sensors

Stepping operation

Switch 10: Number of steps

0

1

2

3

4 - 9

S

wit

ch 1

6

Stepping operation, contact type 1,
Start-sequence: stepping and start

selec

table b

y

key

swit

ch

1 st

ep

2 st

ep

3 st

ep

not allo

w

ed (fault 5)

7

Stepping operation, contact type 2,
Start-sequence: stepping and start

8

Stepping operation, contact type 1,
Start-sequence: start and stepping

9

Stepping operation, contact type 2,
Start-sequence: start and stepping

plate

M2929