Rockwell Automation 440R Lichtgittermodul MSR22LM mit umschaltbaren Funktionen Light curtain controller User Manual
Page 12
 
12
Operation mode: Protective operation with muting
Using 2 muting sensors
Using 4 muting sensors
Operation mode: Protective operation with muting
e.g. conveyors
 1 or 2 light curtains
 Muting of light curtain 1
 2 or 4 muting sensors with diff erent input sequences
 Auto or manual start
 Override via start button
Muting
Muting means to disable temporarily the protective function of a light 
curtain. This function is used to transport material through a light curtain 
without stopping the machine. The diff erentiation between material and 
persons is done by additional muting sensors which have to create a certain 
switching sequence together with the light curtain when material passes 
the light curtain. The muting control starts then the muting cycle for the 
time the material is passing the light curtain. It must not be possible that 
a person activates the muting sensors in the same switching sequence as 
the material. To realise this function 2 diff erent switching sequences can be 
chosen on MSR22LM either with 2 or 4 muting sensors. This makes sure that 
if a person passes the light curtain the dangerous movement of the machine 
is stopped immediately. The muting cycle is indicated by a muting lamp that 
is controlled and monitored by the MSR22LM. The maximum muting time 
can be set in 10 steps between 10 s and infi nite.
If the light curtain is still interrupted after the max. permitted muting time 
e.g. by blocked material the contacts K1, K2 open and the muting lamp as 
well as the LED run 1 show failure code 4.
Starting by pressing the start button is only possible if the muting lamp is 
working and the light curtain to be muted is free of interruption. During 
the muting cycle a wrong switching sequence or exceeding the maximum 
muting time leads to failure code 4. This failure can only be reset by pressing 
the start button. The muting sensors have to be installed in a way, that 
the correct sequence cannot be achieved manually or by passing the light 
curtain (see IEC/EN 61 491-1).
Possible settings
Switch 10:
a = maximum muting time
b = maximum synchronising time
0
1
2
3
4
5
6
7
8
9
S
wit
ch 1
2
LC S1 Auto,
muting 2 sensors
a: 10 s / b: 3 s
a: 20 s / b: 3 s
a: 30 s / b: 3 s
a: 1 min / b: 6 s
a: 5 min / b: 30 s
a: 15 min / b: 90 s
a: 30 min / b: 3 min
a: 1 h / b: 3 min
a: 8 h / b: 3 min
no muting time monit
oring
3
LC S1 Manu,
muting 2 sensors
4
LC S1 Auto,
muting 4 sensors
5
LC S1 Manu,
Muting 4 sensors
Override
If the monitored area is blocked by transported material and the outputs 
K1, K2 are switched off , this is indicated by fast fl ashing (approx. 3 Hz) of the 
muting lamp. The operator can activate the outputs K1, K2 by pressing the 
start button for more than 3 s for a maximum time of 12 s until the muting 
sensor are again inactive or the start button is released again.
Example for an override cycle when muting with 2 sensors
muted LC1
muting sensor 1
muting sensor 2
muting lamp
M9477
safety relay K1/K2
start button
unmuted LC2
: on
: flashing
: fast flashing (3Hz)
error code
1
2
t=3 S
override
t < 12 S