Rockwell Automation T8082 Trusted Toolset Suite User Manual

Page 36

Advertising
background image

Trusted

TM

Toolset Suite T8082

Issue 14 Feb 10

PD-T8082

36

Note that de-energised short circuit templates will not work on older 5V HIU hardware builds. An
attempt to swap from a 3.3V module with this template, to a 5V module, will fail.

2.3.21.

De-energised Short Circuit Detection Template Editor

From the Template Creation window, select the De-energised Short Circuit Detection option,
module voltage and number of channels. Enter a description for the template. Select the Edit button on
the display. This will cause the De-Energised Short Circuit Detection editor window to be displayed as
shown in Figure 19 below.

Figure 19 De-energised Short Circuit Detection Template Editor

To change the channel line monitoring, point and click right-hand mouse button on the channel
required to get the line monitor selection menu. Select either 40 or off. Selecting Select All (or Ctrl–A
or the Select All icon) allows all channels to be set together.

When the correct channel selections have been entered, the user must select the OK button. This will
return the user to the Template Creation window which permits the newly created template to be
saved. The filename must not include any spaces. Underscores are recommended.

Advertising