Trusted, Toolset suite t8082 – Rockwell Automation T8082 Trusted Toolset Suite User Manual

Page 79

Advertising
background image

Trusted

TM

Toolset Suite T8082

Issue 14 Feb 10

PD-T8082

79

watchdogs on 8480 modules and the watchdog times on these modules should be adjusted. (see
TN20057).

Minimum scan time

32ms

This is set to allow room for communications traffic and background tasks. It is especially important on
some hybrid systems where legacy I/O scanning is asynchronous to main processor scanning.

Scan time estimations are given in PD-8110B. Note that these tend to be pessimistic and are only
estimates.

Maximum total variables of any type

65,535

This is described in TA20004 and a method for determining the limit is given in AN-80011. This covers
all variables of any one type (Boolean, analogue, timer etc.) across the whole application, including
internal temporary variables to reference wires and connection corners etc. (see AN-80009).

Maximum instance number

9999

Each FBD program has a numbering scheme in its source code (the application file program.lsf) for
variables, functions/function blocks and wires. The numbers are allocated sequentially from the
highest, and lower numbers are not reused. When the numbers reach 10000 the number rolls over and
the online update manager cannot recognise them; it will always apply an online update and some
function block local variables will be reset. AN-80009 describes a method to reset these numbers,
essentially by cutting and pasting the logic.

Maximum FBD program size

Approximately 75% of diagram area

The maximum FBD program complexity (as measured by the size of the application file program.lsf)
and the proportion of space used by the program on the diagram, do not have clear limits. At large
sizes, a program will appear to compile properly but it is possible that not all wires on the diagram will
work. It is recommended to keep the program to less than 75% of the available diagram area, and to
turn off power flow debugging on programs larger than 50% of the area (because power flow
debugging adds many temporary variables).

Maximum application or program name 8 characters

Maximum variable name

32 characters (at TUV 3.5 toolset)

16 characters (before TUV 3.5 toolset)

Maximum conversion table points

32 per table

Maximum conversion tables

127

Maximum programs in an application

255

Maximum levels of program hierarchy 20 (depth of subprogram nesting)

Maximum FBD diagram width

200 columns (see above for height)

Maximum I/O connection boards

256

Maximum function (block) parameters 32 (total of inputs and outputs)

The ISaGRAF users’ guide lists other limits but those detailed above will be the first to be encountered.