This section describes wire, power and grounding requirements for an XM 
system. 
Wiring Requirements
Use solid or stranded wire. All wiring should meet the following specifications:
• 14 to 22 AWG copper conductors without pretreatment; 8 AWG
required for grounding the DIN rail for electromagnetic interference 
(emi) purposes
• Recommended strip length 8 millimeters (0.31 inches)
• Minimum insulation rating of 300V
• Soldering the conductor is forbidden
• Wire ferrules can be used with stranded conductors; copper ferrules
recommended
Power Requirements
Before installing your module, calculate the power requirements of all modules 
interconnected via their side connectors. The total current draw through the 
side connector cannot exceed 3A. Refer to the specifications for the specific 
modules for power requirements. 
Figure 2.1 is an illustration of wiring modules using separate power 
connections.
ATTENTION
See the XM Documentation and Configuration Utility CD 
for Hazardous Locations installation drawings. The XM 
Documentation and Configuration Utility CD is packaged 
with the XM modules.
ATTENTION
A separate power connection is necessary if the total 
current draw of the interconnecting modules is greater than 
3A.