Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual
Page 86
 
Rockwell Automation Publication GMSI10-UM009D-EN-P - June 2011
86 DeviceNet Objects
7
Get/Set
Delay
USINT
The time period that the 
voting logic must be true 
before the relay is 
activated.
0 to 25.5 seconds
(specified in tenths of seconds)
8
Get/Set
Name
STRING2
A name to help identify 
the relay.
18 characters maximum
9
Get/Set
Alarm Level
BYTE
Specifies what alarm 
status values will cause 
the relay to activate.
0 = Normal
1 = Alert
2 = Danger
3 = Disarm
4 = Xdcr Fault
5 = Module Fault
6 = Tachometer Fault
7 = Unknown
12
Get/Set
Logic
USINT
Indicates the number of 
associated alarms that 
must have a status value 
specified by Alarm Level 
in order to activate the 
relay.
The number of alarms that must 
meet or exceed the Alarm 
Level condition(s) before the 
relay is activated.
For example if there are 8 
alarms in the Alarm List and 
the Logic attribute is set to 3, 
the relay will activate when any 
3 or more of the 8 alarm 
statuses exist at the same time. 
13
Get/Set
 
Alarm List
STRUCT of
A list of Alarms used to 
determine the relay 
status.
Number
USINT
The number of alarms in 
the list.
The number of 3 USINT sets that 
follow (1-16). The USINT specify 
the device from which the alarm 
comes from and the location 
within that device’s COS 
Assembly where the particular 
alarm status is found.
List
Array of 
STRUCT of
MAC ID USINT
Specifies the device that 
maintains the alarm.
0-63
Byte Offset USINT
Specifies the byte in the 
device’s COS Assembly 
that contains the alarm 
status.
0-255
Bit Offset USINT
Specifies the bit within 
the byte where the alarm 
status value begins.
Table C.26 Relay Object Instance Attributes
Attr ID
Access 
Rule
Name Data
Type
Description
Semantics